Internaltional Fire Code Fire Flow Requirements For Buildings

Nashville Fire Department

 
 
   

 


 

  Internaltional Fire Code Fire Flow Requirements For Buildings.xls

 
  Download this file in PDF format: 

SECTION B105
FIRE-FLOW REQUIREMENTS FOR BUILDINGS
B105.1 One- and two-family dwellings.
The minimum fire-flow requirements for one- and two-family dwellings having a fire-flow calculation area which does not exceed 3,600 square feet (344.5 m2) shall be 1,000 gallons per minute (3785.4 L/min). Fire-flow and flow duration for dwellings having a fire-flow calculation area in excess of 3,600 square feet (344.5 m2) shall not be less than that specified in Table B105.1.                                                                                            
All new one- and two-family and townhouse dwellings not covered by Exception No. 1, Exception No. 2, or Exception No. 3 of B105.1 shall be required to meet the fire-flow requirements of Appendix B.
Exception No.1: A reduction in required fire flow of 50 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system.
Exception No. 2: One- and two-family and townhouse dwellings not greater than 3600 square feet which are constructed on existing, legal building lots, as defined in Section 202, are not subject to Appendix B if they:
1   . Meet definition #1 of "existing, legal building lot" and meet the fire-flow requirements of the Insurance Services Office (ISO) Formula for Needed Fire Flow; or
2   . Meet definition #1 of "existing legal building lot" and have a fire hydrant within 500 feet of all parts of the home, measured by way of hard surface road, and the hydrant flows at least 750 gpm with 20 psi residual pressure; or
3   . Meet definition #1 of "existing legal building lot" and have a fire hydrant within 500 feet of all parts of the home, measured by way of hard surface road, and the hydrant flows less than 750 gpm but not less than 500 gpm with 20 psi residual pressure and there is a secondary fire hydrant within 1,000 feet of the home that flows no less than 1,000 gpm with 20 psi residual pressure; or
4   . Meet definition #2 or #3 of "existing building lot" in which case they shall meet the fire-flow requirements set forth by the fire code official at the time the plat was approved or preliminarily approved.  In the event the fire-flow requirements were not noted at the time of approval or preliminary approval, then Appendix B shall apply unless:
4.1 There is a fire hydrant within 500 feet of all parts of the home, measured by way of hard surface road, and the hydrant flows at least 750 gpm with 20 psi residual pressure: or
4.2  There is a fire hydrant within 500 feet of all parts of the home, measured by way of hard surface road, and the hydrant flows less than 750 gpm but not less than 500 gpm with 20 psi residual pressure and there is a secondary fire hydrant within 1,000 feet of the home that flows no less than 1,000 gpm with 20 psi residual pressure; or
  4.3 The fire-flow requirements of the Insurance Service Office (ISO) Formula for Needed Fire Flow are met.
Exception No. 3: One and two-family townhouse dwellings which exceed 3,600 square feet and which are    constructed on "existing, legal building lots" shall meet either the fire-flow requirements of the Insurance Service Office (ISO) Formula for Needed Fire Flow or Appendix B of the International Fire Code.
NOTE: See International Fire Code amendments for definitions of an existing legal building lot.
TABLE B105.1
MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGSa
  FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW (gallons per minute)c FLOW DURATION (hours)
     
Type IA and IBb Type IIA and IIIAb Type IV and V-Ab Type IIB and IIIBb Type V-Bb    
  0-22,700 0-12,700 0-8,200 0-5,900 0-3,600 1,500  
22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750  
30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000 2
38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250  
48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500  
59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750  
70,901-83,700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000  
83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250 3
97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500  
112,701-128,700 63,401-72,400 40,601-46,400 29,301-33,500 18,001-20,600 3,750  
128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20,601-23,300 4,000  
145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250  
164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29,300 4,500  
183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750  
203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000  
225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250  
247,701-271,200 139,401-152,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500  
271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 5,750 4
295,901-Greater 166,501-Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000  
115,801-125,500 83,701-90,600 51,501-55,700 6,250  
125,501-135,500 90,601-97,900 55,701-60,200 6,500  
135,501-145,800 97,901-106,800 60,201-64,800 6,750  
145,801-156,700 106,801-113,200 64,801-69,600 7,000  
156,701-167,900 113,201-121,300 69,601-74,600 7,250  
167,901-179,400 121,301-129,600 74,601-79,800 7,500  
179,401-191,400 129,601-138,300 79,801-85,100 7,750  
191,401-Greater 138,301-Greater 85,101-Greater 8,000  
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.
a. The minimum required fire flow shall be allowed to be reduced by 25 percent for Group R.
b. Types of construction are based on the International Building Code.
c. Measured at 20 psi.
B105.2 Buildings other than one- and two-family dwellings.
The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table B105.1.
Exception: A reduction in required fire-flow of up to 75 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. The resulting fire-flow shall not be less than 1,500 gallons per minute (5678 L/min) for the prescribed duration as specified in Table B105.1.